Samwon Tech TEMI850 Instrukcja Obsługi Strona 109

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 126
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 108
SAMWONTECH
3rd Edition of TEMI880 IM : Aug. 22. 2005 Page 107 /
123
4.4.4.4 Pattern copy/delete & Segment insert/delete
Program pattern copy
1 Set object pattern number on D1000
2 Set target pattern number on D1001
3 Set PT COPY TRIGGER('4') on D1003
4 Read D1004 data and then wait until DONE('1')
Program pattern delete
1 Set delete pattern number on D1000
2 Set PT DEL TRIGGER('5') on D1003
3 Read D1004 data and then wait until DONE('1')
Insert segment
1 Set program pattern number on D1000
2 Set insert pattern number on D1002
3 Set Temp. TSP, Humi. TSP and segment time on D1010~D1012
4 Set SEG INSERT TRIGGER('6') on D1003
5 Read D1004 data and then wait until DONE('1')
Delete segment
1 Set program pattern number on D1000
2 Set delete segment number on D1002
3 Set SEG DEL TRIGGER('7') on D1003
4 Read D1004 data and then wait until DONE('1')
Przeglądanie stron 108
1 2 ... 104 105 106 107 108 109 110 111 112 113 114 ... 125 126

Komentarze do niniejszej Instrukcji

Brak uwag